Addressing intra-area oscillations and frequency stability after DC segmentation of a large AC power system

Mathieu Robin, Javier Renedo, , Juan Carlos Gonzalez-Torres, Aurelio Garcia-Cerrada, , Luis Rouco, , Abdelkrim Benchaib, and Pablo Garcia-Gonzalez This is an unabridged draft of the paper submitted on 14th June 2024 to the Journal of Modern Power Systems and Clean Energy and currently under review This work is supported by the French Government under the program Investissements d’Avenir (ANEITE-002-01).
Abstract

In the last decades, various events have shown that electromechanical oscillations are a major concern for large interconnected Alternating Current (AC) power systems. Segmentation of AC power systems with High Voltage Direct Current (HVDC) systems (DC segmentation, for short) is a method that consists in turning large AC grids into a set of asynchronous AC clusters linked by HVDC links. It is a promising solution to mitigate electromechanical oscillations and other issues. In particular, an appropriately placed DC segmentation can stop a selected inter-area electromechanical oscillation mode. However, without supplementary controllers, DC segmentation will not contribute to the dam** of the intra-area oscillation modes in the remaining AC clusters and will deteriorate the frequency stability of the power system. This paper aims at filling this gap and proposes the use of DC segmentation with HVDC systems based on Voltage Source Converters (VSC-HVDC) with supplementary controllers in the converter stations: (a) active-power supplementary controllers for frequency support among the asynchronous AC clusters and (b) a reactive-power supplementary controllers for Power Oscillation Dam** (POD-Q), in order to damp the intra-area oscillation modes. The proposed supplementary controllers and their design will be presented, and their efficiency will be demonstrated on the Nordic 44 test system with DC segmentation by means of non-linear time-domain simulation and small-signal stability analysis.

Index Terms:
HVAC/HVDC, Voltage Source Converter, VSC-HVDC, power system stability, DC segmentation, power oscillation dam**, POD-Q, frequency control.

I Introduction

Alternating Current (AC) technology is currently the dominant technology for the transmission and distribution of electrical energy. However, the transmission capability with High Voltage Alternating Current (HVAC) is limited by some technical aspects that can be overcome by the High Voltage Direct Current (HVDC) transmission technology that has been developed in the last decades [1]. Thus, many point-to-point HVDC links are already in operation around the world, and even more are planned or under construction [2, 3]. This means that electrical grids are evolving toward hybrid HVAC/HVDC power systems with a growing share of HVDC transmission [4].

In parallel with the development of HVDC links, power systems have also become more and more interconnected creating large AC synchronous electrical grids. This action sums the interconnected systems’ inertia values, improves frequency stability and increases the reliability of the resulting power systems. However, with the introduction of new economical objectives, power systems are operated closer to their stability limits and the risk of severe disruptions is increasing rapidly. For example, in the last decade, various events have shown that electromechanical oscillations are now a bigger threat than ever [5]. Electromechanical oscillations are a rotor angle stability phenomenon under small perturbations in a frequency range between 0.1 and 2Hz (low-frequency oscillations) [6].

Traditionally, the most cost-effective solution to damp electromechanical oscillations in power systems has been the use of supplementary controllers attached in the different devices of the power system. The most extended solution is the implementation of Power System Stabilizers (PSS) in synchronous machines [7]. Nevertheless, supplementary Power Oscillation Dam** (POD) controllers in renewable power plants [8, 9], Energy Storage Systems (ESS) [10], Flexible Alternating Current Transmission Systems (FACTS) [11, 12], HVDC systems based on Line Commutated Converters (LCC-HVDC) [13] and VSC-HVDC [14, 15, 16, 17, 18, 19] systems have also proved to be effective solutions.

However, in stressed power systems electromechanical oscillations with low dam** ratio can arise in certain scenarios, even if dedicated supplementary controllers are attached in the different devices of the power system. In these situations, corrective actions may need to be taken, such as reduction of the power exchange between the different areas, for example [5]. In extremely severe cases, other corrective actions such as intentional islanding have been proposed. Intentional islanding will disconnect selected lines to split a grid into a set of stable areas – called islands – that are reconnected once the fault and its propagation have been properly addressed [20, 21, 22, 23].

Intentional islanding is only an operational action. However, recent work has analysed segmentation of AC power systems with VSC-HVDC links (DC segmentation, for short) to mitigate electromechanical oscillations [24], which is a potential solution in stressed power systems. DC segmentation was first proposed in [25] and consists in segmenting a large AC asynchronous grid into a set of AC asynchronous grids linked by HVDC links. DC segmentation is a promising application of VSC-HVDC to tackle severe instability problems or to improve the operation of the system [26]. For example, a first DC segmentation project was carried out in China in 2016  [27] to prevent potential overloading of the inter-area AC lines in case of contingency. There are different applications of DC segmentation. For example, it has the capacity to limit the propagation of disturbances [28, 29, 30]. Therefore, it could limit the risk of cascading failures and blackouts [25]. This effect of DC segmentation has been confirmed in [31, 32]. Additionally, DC segmentation can also improve the power exchange capacity between different areas [25, 33, 34].

Regarding electromechanical oscillations, the work in [24] proposed an algorithm to obtain a DC-segmentation architecture for a given AC power system, targeted to mitigate electromechanical oscillations. The work in [35] presented a comprehensive analysis of the impact of DC segmentation on transient stability, electromechanical-oscillation dam** and frequency stability in power systems. It showed that DC segmentation, where VSC-HVDC systems are controlled with constant power set points, could improve transient stability and the dam** of electromechanical oscillations (the DC segments act as firewalls), while the overall frequency stability is jeopardised, because each of the resulting asynchronous AC clusters have lower amounts of inertia and primary frequency support. Since in [24] the VSC-HVDC links used for DC segmentation where controlled with constant active- (P) and reactive-power (Q) injections, there is still room for further improvements.

Hence, given a power system with DC segmentation targeted to damp electromechanical oscillations (as in [24]), the target inter-area mode is eliminated. However, the following questions remain open:

  • Could the dam** ratio of the intra-area electromechanical modes of the remaining AC clusters be increased?

  • Could the overall frequency stability of the resulting DC-segmented system be improved?

Along these lines, the contributions of this paper are as follows:

  • Investigation of the use of supplementary reactive-power controllers in the VSC-HVDC systems of the DC-segmented system to damp intra-area oscillations in the remaining clusters (POD-Q controllers, for short). Two POD-Q controllers are analysed: (a) one using local frequency as input signal (based on previous proposals) and (b) another one using the frequency of the Centre Of Inertia (COI) of each AC cluster, which is a new proposal of this work.

  • Investigation of the use of supplementary active-power/frequency controllers (FC) in the VSC-HVDC systems of the DC-segmented system to improve frequency stability.

  • Proposal of the concept of numerical eigenvalue sensitivity, which is used in the design of POD-Q controllers. This concept is an approximation of the theoretical eigenvalue sensitivity concept and it can facilitate its implementation.

Notice that, although POD controllers [15] and frequency controllers [36, 37, 38] in VSC-HVDC systems have been analysed in previous work, their application to a DC-segmented system has not received enough attention in previous work. This is essential to fully exploit DC-segmentation concept for the particular application for the mitigation of electromechanical oscillations, which is the main objective of this paper.

II DC segmentation of power systems and VSC-HVDC systems

Fig. 1-a shows a schematic diagram of an AC power system and Fig. 1-b shows the power system after DC segmentation, where an AC line has been replaced by a VSC-HVDC link, decoupling the two remaining AC systems. Notice that, in general, a DC-segmented system could have more than one VSC-HVDC link decoupling the asynchronous AC clusters of the system. This paper focuses on the application of DC segmentation for the mitigation of electromechanical oscillations. Along this line, the work in [24] proposed an algorithm to obtain a DC-segmentation architecture to mitigate the critical inter-area oscillation of the original AC power system. The algorithm used the concept of electromechanical-oscillation path proposed in [39]. The algorithm selects the AC lines to be replaced with point-to-point VSC-HVDC links, leading to a DC-segmented system with asynchronous AC clusters. This DC segmentation fully suppresses the target inter-area electromechanical mode, without impacting the local electromechanical modes of the asynchronous clusters. The work in [24] analysed DC segmentation with constant power of the VSC-HVDC links. This work goes a step further as it will consider supplementary controllers to (a) damp intra-area oscillations in the asynchronous AC clusters and (b) to provide frequency support among the asynchronous AC clusters, as it will be described in Section III.

Refer to caption
Figure 1: (a) AC power system and (b) DC-segmented power system.

Electromechanical-type models of VSC-HVDC systems, also known as Root-Mean-Square (RMS) models, are used, following the guidelines of [40], as illustrated in Fig. 2. Every VSC station is modelled as a voltage source at their AC side connected by a series impedance, that aggregates the AC reactor and the transformer, and they are seen as current injections at their DC side; the AC and DC sides are coupled by the energy conservation principle. VSC stations are controlled with conventional vector control with Grid-Following (GFL) control and the model includes their operation limits, as described in [40]. In each VSC-HVDC link, one VSC station controls its active-power injection, while the other one controls the DC voltage. Meanwhile, each VSC station controls independently its reactive power injection. Finally, the DC grid is represented with the equivalent capacitor at each DC bus and with the series resistances and inductances of the DC lines.

Refer to caption
Figure 2: Model of a VSC station.

III Supplementary controllers

The following supplementary controllers in VSC-HVDC links of the DC-segmented case will be considered:

  • Frequency Control (FC): The objective is to provide frequency support between the asynchronous AC areas through the VSC-HVDC links.

  • Power Oscillation Dam** (POD) controllers for the Q injections (POD-Q): The objective is to contribute to damp intra-area oscillations in the asynchronous AC areas by means of Q-modulation in the VSC stations of the DC segments.

III-A Frequency Controllers (FC)

In FC, the P set point of the VSC station that controls the active power through each DC segment (VSC-i𝑖iitalic_i) is given by:

Pac,i=Pac,i0+ΔPac,iref,FCsuperscriptsubscript𝑃𝑎𝑐𝑖superscriptsubscript𝑃𝑎𝑐𝑖0Δsuperscriptsubscript𝑃𝑎𝑐𝑖𝑟𝑒𝑓𝐹𝐶P_{ac,i}^{*}=P_{ac,i}^{0}+\Delta P_{ac,i}^{ref,FC}italic_P start_POSTSUBSCRIPT italic_a italic_c , italic_i end_POSTSUBSCRIPT start_POSTSUPERSCRIPT ∗ end_POSTSUPERSCRIPT = italic_P start_POSTSUBSCRIPT italic_a italic_c , italic_i end_POSTSUBSCRIPT start_POSTSUPERSCRIPT 0 end_POSTSUPERSCRIPT + roman_Δ italic_P start_POSTSUBSCRIPT italic_a italic_c , italic_i end_POSTSUBSCRIPT start_POSTSUPERSCRIPT italic_r italic_e italic_f , italic_F italic_C end_POSTSUPERSCRIPT (1)

where Pac,i0superscriptsubscript𝑃𝑎𝑐𝑖0P_{ac,i}^{0}italic_P start_POSTSUBSCRIPT italic_a italic_c , italic_i end_POSTSUBSCRIPT start_POSTSUPERSCRIPT 0 end_POSTSUPERSCRIPT is a constant P set-point value, and ΔPac,iref,FCΔsuperscriptsubscript𝑃𝑎𝑐𝑖𝑟𝑒𝑓𝐹𝐶\Delta P_{ac,i}^{ref,FC}roman_Δ italic_P start_POSTSUBSCRIPT italic_a italic_c , italic_i end_POSTSUBSCRIPT start_POSTSUPERSCRIPT italic_r italic_e italic_f , italic_F italic_C end_POSTSUPERSCRIPT is the supplementary P set-point value provided by the FC.

Fig. 3 shows the block diagram of the FC, based on strategy FC-WAF proposed in [37] for multi-terminal VSC-HVDC systems (VSC-MTDC), which uses the average frequency of the VSC-MTDC as set point (ω=ω¯superscript𝜔¯𝜔\omega^{*}=\bar{\omega}italic_ω start_POSTSUPERSCRIPT ∗ end_POSTSUPERSCRIPT = over¯ start_ARG italic_ω end_ARG) for the frequency controller. The FC uses a proportional controller with gain KFC,isubscript𝐾𝐹𝐶𝑖K_{FC,i}italic_K start_POSTSUBSCRIPT italic_F italic_C , italic_i end_POSTSUBSCRIPT, a low-pass filter with time constant TFC,isubscript𝑇𝐹𝐶𝑖T_{FC,i}italic_T start_POSTSUBSCRIPT italic_F italic_C , italic_i end_POSTSUBSCRIPT and a saturation parameter ±ΔPac,imaxplus-or-minusΔsuperscriptsubscript𝑃𝑎𝑐𝑖𝑚𝑎𝑥\pm\Delta P_{ac,i}^{max}± roman_Δ italic_P start_POSTSUBSCRIPT italic_a italic_c , italic_i end_POSTSUBSCRIPT start_POSTSUPERSCRIPT italic_m italic_a italic_x end_POSTSUPERSCRIPT. The frequency set point for the FC is given by:

ω=ω¯=ωi+ωj2superscript𝜔¯𝜔subscript𝜔𝑖subscript𝜔𝑗2\omega^{*}=\bar{\omega}=\frac{\omega_{i}+\omega_{j}}{2}italic_ω start_POSTSUPERSCRIPT ∗ end_POSTSUPERSCRIPT = over¯ start_ARG italic_ω end_ARG = divide start_ARG italic_ω start_POSTSUBSCRIPT italic_i end_POSTSUBSCRIPT + italic_ω start_POSTSUBSCRIPT italic_j end_POSTSUBSCRIPT end_ARG start_ARG 2 end_ARG (2)

where ωisubscript𝜔𝑖\omega_{i}italic_ω start_POSTSUBSCRIPT italic_i end_POSTSUBSCRIPT and ωjsubscript𝜔𝑗\omega_{j}italic_ω start_POSTSUBSCRIPT italic_j end_POSTSUBSCRIPT are the frequency measured at the two AC terminals of the VSC-HVDC link (in pu).

Refer to caption
Figure 3: Frequency Controller (FC) using FC-WAF.

Notice that in point-to-point VSC-HVDC links, strategy FC-WAF [37] is equivalent a FC controller proportional to the frequency difference between the frequencies of each terminal of the link as long as KFC,i=KFC,i/2superscriptsubscript𝐾𝐹𝐶𝑖subscript𝐾𝐹𝐶𝑖2K_{FC,i}^{\prime}=K_{FC,i}/2italic_K start_POSTSUBSCRIPT italic_F italic_C , italic_i end_POSTSUBSCRIPT start_POSTSUPERSCRIPT ′ end_POSTSUPERSCRIPT = italic_K start_POSTSUBSCRIPT italic_F italic_C , italic_i end_POSTSUBSCRIPT / 2:

ΔPac,iref,FCΔsuperscriptsubscript𝑃𝑎𝑐𝑖𝑟𝑒𝑓𝐹𝐶\displaystyle\Delta P_{ac,i}^{ref,FC}roman_Δ italic_P start_POSTSUBSCRIPT italic_a italic_c , italic_i end_POSTSUBSCRIPT start_POSTSUPERSCRIPT italic_r italic_e italic_f , italic_F italic_C end_POSTSUPERSCRIPT =\displaystyle== KFC,i1+sTFC,i(ω¯ωi)subscript𝐾𝐹𝐶𝑖1𝑠subscript𝑇𝐹𝐶𝑖¯𝜔subscript𝜔𝑖\displaystyle\frac{K_{FC,i}}{1+sT_{FC,i}}(\bar{\omega}-\omega_{i})divide start_ARG italic_K start_POSTSUBSCRIPT italic_F italic_C , italic_i end_POSTSUBSCRIPT end_ARG start_ARG 1 + italic_s italic_T start_POSTSUBSCRIPT italic_F italic_C , italic_i end_POSTSUBSCRIPT end_ARG ( over¯ start_ARG italic_ω end_ARG - italic_ω start_POSTSUBSCRIPT italic_i end_POSTSUBSCRIPT )
=\displaystyle== KFC,i1+sTFC,i[ωi+ωj2ωi]subscript𝐾𝐹𝐶𝑖1𝑠subscript𝑇𝐹𝐶𝑖delimited-[]subscript𝜔𝑖subscript𝜔𝑗2subscript𝜔𝑖\displaystyle\frac{K_{FC,i}}{1+sT_{FC,i}}\big{[}\frac{\omega_{i}+\omega_{j}}{2% }-\omega_{i}\big{]}divide start_ARG italic_K start_POSTSUBSCRIPT italic_F italic_C , italic_i end_POSTSUBSCRIPT end_ARG start_ARG 1 + italic_s italic_T start_POSTSUBSCRIPT italic_F italic_C , italic_i end_POSTSUBSCRIPT end_ARG [ divide start_ARG italic_ω start_POSTSUBSCRIPT italic_i end_POSTSUBSCRIPT + italic_ω start_POSTSUBSCRIPT italic_j end_POSTSUBSCRIPT end_ARG start_ARG 2 end_ARG - italic_ω start_POSTSUBSCRIPT italic_i end_POSTSUBSCRIPT ]
=\displaystyle== KFC,i/21+sTFC,i(ωjωi)=KFC,i1+sTFC,i(ωjωi).subscript𝐾𝐹𝐶𝑖21𝑠subscript𝑇𝐹𝐶𝑖subscript𝜔𝑗subscript𝜔𝑖superscriptsubscript𝐾𝐹𝐶𝑖1𝑠subscript𝑇𝐹𝐶𝑖subscript𝜔𝑗subscript𝜔𝑖\displaystyle\frac{K_{FC,i}/2}{1+sT_{FC,i}}(\omega_{j}-\omega_{i})=\frac{K_{FC% ,i}^{\prime}}{1+sT_{FC,i}}(\omega_{j}-\omega_{i}).divide start_ARG italic_K start_POSTSUBSCRIPT italic_F italic_C , italic_i end_POSTSUBSCRIPT / 2 end_ARG start_ARG 1 + italic_s italic_T start_POSTSUBSCRIPT italic_F italic_C , italic_i end_POSTSUBSCRIPT end_ARG ( italic_ω start_POSTSUBSCRIPT italic_j end_POSTSUBSCRIPT - italic_ω start_POSTSUBSCRIPT italic_i end_POSTSUBSCRIPT ) = divide start_ARG italic_K start_POSTSUBSCRIPT italic_F italic_C , italic_i end_POSTSUBSCRIPT start_POSTSUPERSCRIPT ′ end_POSTSUPERSCRIPT end_ARG start_ARG 1 + italic_s italic_T start_POSTSUBSCRIPT italic_F italic_C , italic_i end_POSTSUBSCRIPT end_ARG ( italic_ω start_POSTSUBSCRIPT italic_j end_POSTSUBSCRIPT - italic_ω start_POSTSUBSCRIPT italic_i end_POSTSUBSCRIPT ) .

With the FC of Fig. 3, frequency support among the asynchronous AC areas through the VSC-HVDC links is achieved, independently of the location of the disturbance, since the FC uses frequency measurements at both ends of the VSC-HVDC links.

III-B POD-Q controllers

Two POD controllers for the reactive-power injections of the VSC stations (POD-Q) will be analysed and compared in this work:

  • POD-Q-LF: It modulates Q injections of the VSC and it using local measurement of the frequency at the AC connection point.

  • POD-Q-FCOI: It modulates Q injection of the VSC using global measurements of the frequency of the Centre Of Inertia (COI) of the AC area at which the VSC is connected to.

The Q set point of each VSC-i𝑖iitalic_i is given by:

Qac,i=Qac,i0+ΔQac,iref,PODsuperscriptsubscript𝑄𝑎𝑐𝑖superscriptsubscript𝑄𝑎𝑐𝑖0Δsuperscriptsubscript𝑄𝑎𝑐𝑖𝑟𝑒𝑓𝑃𝑂𝐷Q_{ac,i}^{*}=Q_{ac,i}^{0}+\Delta Q_{ac,i}^{ref,POD}italic_Q start_POSTSUBSCRIPT italic_a italic_c , italic_i end_POSTSUBSCRIPT start_POSTSUPERSCRIPT ∗ end_POSTSUPERSCRIPT = italic_Q start_POSTSUBSCRIPT italic_a italic_c , italic_i end_POSTSUBSCRIPT start_POSTSUPERSCRIPT 0 end_POSTSUPERSCRIPT + roman_Δ italic_Q start_POSTSUBSCRIPT italic_a italic_c , italic_i end_POSTSUBSCRIPT start_POSTSUPERSCRIPT italic_r italic_e italic_f , italic_P italic_O italic_D end_POSTSUPERSCRIPT (4)

where Qac,i0superscriptsubscript𝑄𝑎𝑐𝑖0Q_{ac,i}^{0}italic_Q start_POSTSUBSCRIPT italic_a italic_c , italic_i end_POSTSUBSCRIPT start_POSTSUPERSCRIPT 0 end_POSTSUPERSCRIPT is a constant Q set-point value, and ΔQac,iref,PODΔsuperscriptsubscript𝑄𝑎𝑐𝑖𝑟𝑒𝑓𝑃𝑂𝐷\Delta Q_{ac,i}^{ref,POD}roman_Δ italic_Q start_POSTSUBSCRIPT italic_a italic_c , italic_i end_POSTSUBSCRIPT start_POSTSUPERSCRIPT italic_r italic_e italic_f , italic_P italic_O italic_D end_POSTSUPERSCRIPT is the supplementary Q set-point value provided by POD-Q controller.

The two POD-Q controllers above can be described with the scheme of Fig. 4. The input signal of the controller is the frequency error (in pu) between the frequency set point (ωisuperscriptsubscript𝜔𝑖\omega_{i}^{*}italic_ω start_POSTSUBSCRIPT italic_i end_POSTSUBSCRIPT start_POSTSUPERSCRIPT ∗ end_POSTSUPERSCRIPT) and the frequency measured at the AC connection point of the VSC station (ωisubscript𝜔𝑖\omega_{i}italic_ω start_POSTSUBSCRIPT italic_i end_POSTSUBSCRIPT). The POD-Q controller has a low-pass filter (with time constant TQf,isubscript𝑇𝑄𝑓𝑖T_{Qf,i}italic_T start_POSTSUBSCRIPT italic_Q italic_f , italic_i end_POSTSUBSCRIPT), a wash-out filter (with time constant TQW,isubscript𝑇𝑄𝑊𝑖T_{QW,i}italic_T start_POSTSUBSCRIPT italic_Q italic_W , italic_i end_POSTSUBSCRIPT), a lead/lag filter (with time constants TQ1,isubscript𝑇𝑄1𝑖T_{Q1,i}italic_T start_POSTSUBSCRIPT italic_Q 1 , italic_i end_POSTSUBSCRIPT, TQ2,i=aQ,iTQ1,isubscript𝑇𝑄2𝑖subscript𝑎𝑄𝑖subscript𝑇𝑄1𝑖T_{Q2,i}=a_{Q,i}T_{Q1,i}italic_T start_POSTSUBSCRIPT italic_Q 2 , italic_i end_POSTSUBSCRIPT = italic_a start_POSTSUBSCRIPT italic_Q , italic_i end_POSTSUBSCRIPT italic_T start_POSTSUBSCRIPT italic_Q 1 , italic_i end_POSTSUBSCRIPT, filtering ratio aQ,isubscript𝑎𝑄𝑖a_{Q,i}italic_a start_POSTSUBSCRIPT italic_Q , italic_i end_POSTSUBSCRIPT and NQS,isubscript𝑁𝑄𝑆𝑖N_{QS,i}italic_N start_POSTSUBSCRIPT italic_Q italic_S , italic_i end_POSTSUBSCRIPT lead/lag networks), a controller gain KQ,isubscript𝐾𝑄𝑖K_{Q,i}italic_K start_POSTSUBSCRIPT italic_Q , italic_i end_POSTSUBSCRIPT and a saturation parameter ±ΔQac,imaxplus-or-minusΔsuperscriptsubscript𝑄𝑎𝑐𝑖𝑚𝑎𝑥\pm\Delta Q_{ac,i}^{max}± roman_Δ italic_Q start_POSTSUBSCRIPT italic_a italic_c , italic_i end_POSTSUBSCRIPT start_POSTSUPERSCRIPT italic_m italic_a italic_x end_POSTSUPERSCRIPT.

Refer to caption
Figure 4: POD-Q controller.

III-B1 POD-Q-LF


In POD-Q-LF controller, the frequency set point of Fig. 4 is the nominal frequency in pu: ωi=ω0=1superscriptsubscript𝜔𝑖subscript𝜔01\omega_{i}^{*}=\omega_{0}=1italic_ω start_POSTSUBSCRIPT italic_i end_POSTSUBSCRIPT start_POSTSUPERSCRIPT ∗ end_POSTSUPERSCRIPT = italic_ω start_POSTSUBSCRIPT 0 end_POSTSUBSCRIPT = 1 pu. Hence, it uses local measurements. This scheme of POD-Q controller is based on previous schemes proposed in the literature [41, 10].

III-B2 POD-Q-FCOI


In POD-Q-FCOI controller, proposed in this work, the frequency set point of Fig. 4 is calculated as the frequency of the COI (in pu) of the AC area which station VSC-i𝑖iitalic_i is connected:

ωi=ωCOI,i=kAiHkHTωk, HT=jAiHj.formulae-sequencesuperscriptsubscript𝜔𝑖subscript𝜔𝐶𝑂𝐼𝑖subscript𝑘subscript𝐴𝑖subscript𝐻𝑘subscript𝐻𝑇subscript𝜔𝑘 subscript𝐻𝑇subscript𝑗subscript𝐴𝑖subscript𝐻𝑗\omega_{i}^{*}=\omega_{COI,i}=\sum_{k\in A_{i}}\frac{H_{k}}{H_{T}}\omega_{k},% \mbox{ }H_{T}=\sum_{j\in A_{i}}H_{j}.italic_ω start_POSTSUBSCRIPT italic_i end_POSTSUBSCRIPT start_POSTSUPERSCRIPT ∗ end_POSTSUPERSCRIPT = italic_ω start_POSTSUBSCRIPT italic_C italic_O italic_I , italic_i end_POSTSUBSCRIPT = ∑ start_POSTSUBSCRIPT italic_k ∈ italic_A start_POSTSUBSCRIPT italic_i end_POSTSUBSCRIPT end_POSTSUBSCRIPT divide start_ARG italic_H start_POSTSUBSCRIPT italic_k end_POSTSUBSCRIPT end_ARG start_ARG italic_H start_POSTSUBSCRIPT italic_T end_POSTSUBSCRIPT end_ARG italic_ω start_POSTSUBSCRIPT italic_k end_POSTSUBSCRIPT , italic_H start_POSTSUBSCRIPT italic_T end_POSTSUBSCRIPT = ∑ start_POSTSUBSCRIPT italic_j ∈ italic_A start_POSTSUBSCRIPT italic_i end_POSTSUBSCRIPT end_POSTSUBSCRIPT italic_H start_POSTSUBSCRIPT italic_j end_POSTSUBSCRIPT . (5)

This strategy was motivated by POD-Q-WAF controller proposed in [16] for VSC-MTDC systems embedded in an AC system, which used as frequency set point the weighted-average frequency of the VSC-MTDC system. However, the application and the controller proposed here are different, since the VSC-HVDC are interconnecting asynchronous AC areas, and the frequency of the COI of each AC area are used as frequency set points for POD-Q controllers. In POD-Q-FCOI controller, each VSC compares the frequency set point with ωi=ωCOI,isuperscriptsubscript𝜔𝑖subscript𝜔𝐶𝑂𝐼𝑖\omega_{i}^{*}=\omega_{COI,i}italic_ω start_POSTSUBSCRIPT italic_i end_POSTSUBSCRIPT start_POSTSUPERSCRIPT ∗ end_POSTSUPERSCRIPT = italic_ω start_POSTSUBSCRIPT italic_C italic_O italic_I , italic_i end_POSTSUBSCRIPT with its own frequency (ωisubscript𝜔𝑖\omega_{i}italic_ω start_POSTSUBSCRIPT italic_i end_POSTSUBSCRIPT). Notice that the usefulness of the speed of the COI for power-system-stability-tailored controllers was illustrated in [42].

III-C Design of POD-Q controllers

The method of the design of POD-Q controllers is based on the work in [11], which uses the concept of eigenvalue sensitivities [43]. The work in [16] used this approach for the design of POD controllers in VSC-HVDC systems. As a novelty of this work, the concept of numerical eigenvalue sensitivity is proposed (instead of the theoretical eigenvalue sensitivity), which can facilitate the design of POD controllers in cases with limited information of the state matrices of the linearised system.

It is assumed that a linearised model of the power system is available. A POD-Q controller in VSC-j𝑗jitalic_j will be used to damp a target electromechanical mode i𝑖iitalic_i:

λi0=σi0±jωi0superscriptsubscript𝜆𝑖0plus-or-minussuperscriptsubscript𝜎𝑖0𝑗superscriptsubscript𝜔𝑖0\lambda_{i}^{0}=\sigma_{i}^{0}\pm j\omega_{i}^{0}italic_λ start_POSTSUBSCRIPT italic_i end_POSTSUBSCRIPT start_POSTSUPERSCRIPT 0 end_POSTSUPERSCRIPT = italic_σ start_POSTSUBSCRIPT italic_i end_POSTSUBSCRIPT start_POSTSUPERSCRIPT 0 end_POSTSUPERSCRIPT ± italic_j italic_ω start_POSTSUBSCRIPT italic_i end_POSTSUBSCRIPT start_POSTSUPERSCRIPT 0 end_POSTSUPERSCRIPT (6)

The dam** ratio of the target electromechanical mode of the original system is called ζi0superscriptsubscript𝜁𝑖0\zeta_{i}^{0}italic_ζ start_POSTSUBSCRIPT italic_i end_POSTSUBSCRIPT start_POSTSUPERSCRIPT 0 end_POSTSUPERSCRIPT and the required dam** ratio is called ζidsuperscriptsubscript𝜁𝑖𝑑\zeta_{i}^{d}italic_ζ start_POSTSUBSCRIPT italic_i end_POSTSUBSCRIPT start_POSTSUPERSCRIPT italic_d end_POSTSUPERSCRIPT. Then, the estimated target electromechanical mode can be approximated as:

λid=ζidωi0±jωi0superscriptsubscript𝜆𝑖𝑑plus-or-minussuperscriptsubscript𝜁𝑖𝑑superscriptsubscript𝜔𝑖0𝑗superscriptsubscript𝜔𝑖0\lambda_{i}^{d}=-\zeta_{i}^{d}\omega_{i}^{0}\pm j\omega_{i}^{0}italic_λ start_POSTSUBSCRIPT italic_i end_POSTSUBSCRIPT start_POSTSUPERSCRIPT italic_d end_POSTSUPERSCRIPT = - italic_ζ start_POSTSUBSCRIPT italic_i end_POSTSUBSCRIPT start_POSTSUPERSCRIPT italic_d end_POSTSUPERSCRIPT italic_ω start_POSTSUBSCRIPT italic_i end_POSTSUBSCRIPT start_POSTSUPERSCRIPT 0 end_POSTSUPERSCRIPT ± italic_j italic_ω start_POSTSUBSCRIPT italic_i end_POSTSUBSCRIPT start_POSTSUPERSCRIPT 0 end_POSTSUPERSCRIPT (7)

The sensitivity of electromechanical mode i𝑖iitalic_i to changes in the gain of POD-Q controller j𝑗jitalic_j, KQ,jsubscript𝐾𝑄𝑗K_{Q,j}italic_K start_POSTSUBSCRIPT italic_Q , italic_j end_POSTSUBSCRIPT, is defined as [43]:

Sij=λiKQ,jsubscript𝑆𝑖𝑗subscript𝜆𝑖subscript𝐾𝑄𝑗S_{ij}=\frac{\partial\lambda_{i}}{\partial K_{Q,j}}italic_S start_POSTSUBSCRIPT italic_i italic_j end_POSTSUBSCRIPT = divide start_ARG ∂ italic_λ start_POSTSUBSCRIPT italic_i end_POSTSUBSCRIPT end_ARG start_ARG ∂ italic_K start_POSTSUBSCRIPT italic_Q , italic_j end_POSTSUBSCRIPT end_ARG (8)

Similarly, the non-compensated sensitivity of mode i𝑖iitalic_i to changes in the gain of the non-compensated POD-Q controller j𝑗jitalic_j (SijNCsuperscriptsubscript𝑆𝑖𝑗𝑁𝐶S_{ij}^{NC}italic_S start_POSTSUBSCRIPT italic_i italic_j end_POSTSUBSCRIPT start_POSTSUPERSCRIPT italic_N italic_C end_POSTSUPERSCRIPT) is defined as:

SijNCsuperscriptsubscript𝑆𝑖𝑗𝑁𝐶\displaystyle S_{ij}^{NC}italic_S start_POSTSUBSCRIPT italic_i italic_j end_POSTSUBSCRIPT start_POSTSUPERSCRIPT italic_N italic_C end_POSTSUPERSCRIPT =\displaystyle== Sij(TQ1,j=0)=λiKQ,j|TQ1,j=0subscript𝑆𝑖𝑗subscript𝑇𝑄1𝑗0evaluated-atsubscript𝜆𝑖subscript𝐾𝑄𝑗subscript𝑇𝑄1𝑗0\displaystyle S_{ij}(T_{Q1,j}=0)=\frac{\partial\lambda_{i}}{\partial K_{Q,j}}% \bigg{|}_{T_{Q1,j}=0}italic_S start_POSTSUBSCRIPT italic_i italic_j end_POSTSUBSCRIPT ( italic_T start_POSTSUBSCRIPT italic_Q 1 , italic_j end_POSTSUBSCRIPT = 0 ) = divide start_ARG ∂ italic_λ start_POSTSUBSCRIPT italic_i end_POSTSUBSCRIPT end_ARG start_ARG ∂ italic_K start_POSTSUBSCRIPT italic_Q , italic_j end_POSTSUBSCRIPT end_ARG | start_POSTSUBSCRIPT italic_T start_POSTSUBSCRIPT italic_Q 1 , italic_j end_POSTSUBSCRIPT = 0 end_POSTSUBSCRIPT
=\displaystyle== |SijNC|φijNCsuperscriptsubscript𝑆𝑖𝑗𝑁𝐶superscriptsubscript𝜑𝑖𝑗𝑁𝐶\displaystyle|S_{ij}^{NC}|\angle\varphi_{ij}^{NC}| italic_S start_POSTSUBSCRIPT italic_i italic_j end_POSTSUBSCRIPT start_POSTSUPERSCRIPT italic_N italic_C end_POSTSUPERSCRIPT | ∠ italic_φ start_POSTSUBSCRIPT italic_i italic_j end_POSTSUBSCRIPT start_POSTSUPERSCRIPT italic_N italic_C end_POSTSUPERSCRIPT

The numerical non-compensated eigenvalue sensitivity, proposed in this work, can be calculated as:

S^ijNC=λiNCλi0ΔKQ,jsuperscriptsubscript^𝑆𝑖𝑗𝑁𝐶superscriptsubscript𝜆𝑖𝑁𝐶superscriptsubscript𝜆𝑖0Δsubscript𝐾𝑄𝑗\hat{S}_{ij}^{NC}=\frac{\lambda_{i}^{NC}-\lambda_{i}^{0}}{\Delta K_{Q,j}}over^ start_ARG italic_S end_ARG start_POSTSUBSCRIPT italic_i italic_j end_POSTSUBSCRIPT start_POSTSUPERSCRIPT italic_N italic_C end_POSTSUPERSCRIPT = divide start_ARG italic_λ start_POSTSUBSCRIPT italic_i end_POSTSUBSCRIPT start_POSTSUPERSCRIPT italic_N italic_C end_POSTSUPERSCRIPT - italic_λ start_POSTSUBSCRIPT italic_i end_POSTSUBSCRIPT start_POSTSUPERSCRIPT 0 end_POSTSUPERSCRIPT end_ARG start_ARG roman_Δ italic_K start_POSTSUBSCRIPT italic_Q , italic_j end_POSTSUBSCRIPT end_ARG (10)

where λiNCsuperscriptsubscript𝜆𝑖𝑁𝐶\lambda_{i}^{NC}italic_λ start_POSTSUBSCRIPT italic_i end_POSTSUBSCRIPT start_POSTSUPERSCRIPT italic_N italic_C end_POSTSUPERSCRIPT is the non-compensated eigenvalue, i.e., the new eigenvalue with the POD-Q implemented without its lead/lag filter (TQ1,j=0subscript𝑇𝑄1𝑗0T_{Q1,j=0}italic_T start_POSTSUBSCRIPT italic_Q 1 , italic_j = 0 end_POSTSUBSCRIPT) and with a small gain ΔKQ,jΔsubscript𝐾𝑄𝑗\Delta K_{Q,j}roman_Δ italic_K start_POSTSUBSCRIPT italic_Q , italic_j end_POSTSUBSCRIPT. Naturally, S^ijNCSijNCsuperscriptsubscript^𝑆𝑖𝑗𝑁𝐶superscriptsubscript𝑆𝑖𝑗𝑁𝐶\hat{S}_{ij}^{NC}\approx S_{ij}^{NC}over^ start_ARG italic_S end_ARG start_POSTSUBSCRIPT italic_i italic_j end_POSTSUBSCRIPT start_POSTSUPERSCRIPT italic_N italic_C end_POSTSUPERSCRIPT ≈ italic_S start_POSTSUBSCRIPT italic_i italic_j end_POSTSUBSCRIPT start_POSTSUPERSCRIPT italic_N italic_C end_POSTSUPERSCRIPT.

Fig. 5 shows the geometric interpretation of eigenvalue sensitivities [11, 16]. An effective POD-Q will move the target electromechanical mode to the left-hand side of the complex plane, as illustrated in Fig. 5. The lead/lag filter is used to ensure that the eigenvalue sensitivity has phase as close to 180° as possible, while gain KQ,jsubscript𝐾𝑄𝑗K_{Q,j}italic_K start_POSTSUBSCRIPT italic_Q , italic_j end_POSTSUBSCRIPT (see Fig. 4) is used to move the eigenvalues further to the left-hand side of the complex plane and to achieve the required dam** ratio.

Refer to caption
Figure 5: Geometric interpretation of eigenvalue sensitivities.

The design of the POD-Q controller of each VSC-j𝑗jitalic_j consists of two steps [11]:

  1. 1.

    Design of the lead/lag filter: Its objective is to obtain a phase of the eigenvalue sensitivity (S^ijsubscript^𝑆𝑖𝑗\hat{S}_{ij}over^ start_ARG italic_S end_ARG start_POSTSUBSCRIPT italic_i italic_j end_POSTSUBSCRIPT) as close to 180osuperscript180o180^{{\rm o}}180 start_POSTSUPERSCRIPT roman_o end_POSTSUPERSCRIPT as possible [11]:

    phaselead (φ^ijNC0{\rm phase\;lead}\mbox{ }(\hat{\varphi}_{ij}^{NC}\geq 0roman_phase roman_lead ( over^ start_ARG italic_φ end_ARG start_POSTSUBSCRIPT italic_i italic_j end_POSTSUBSCRIPT start_POSTSUPERSCRIPT italic_N italic_C end_POSTSUPERSCRIPT ≥ 0):

    aQ,j=1sinϕij1+sinϕij1,ϕij=πφ^ijNCNQS,j.formulae-sequencesubscript𝑎𝑄𝑗1subscriptitalic-ϕ𝑖𝑗1subscriptitalic-ϕ𝑖𝑗1subscriptitalic-ϕ𝑖𝑗𝜋superscriptsubscript^𝜑𝑖𝑗𝑁𝐶subscript𝑁𝑄𝑆𝑗a_{Q,j}=\frac{1-\sin\phi_{ij}}{1+\sin\phi_{ij}}\leq 1,\;\phi_{ij}=\frac{\pi-% \hat{\varphi}_{ij}^{NC}}{N_{QS,j}}.italic_a start_POSTSUBSCRIPT italic_Q , italic_j end_POSTSUBSCRIPT = divide start_ARG 1 - roman_sin italic_ϕ start_POSTSUBSCRIPT italic_i italic_j end_POSTSUBSCRIPT end_ARG start_ARG 1 + roman_sin italic_ϕ start_POSTSUBSCRIPT italic_i italic_j end_POSTSUBSCRIPT end_ARG ≤ 1 , italic_ϕ start_POSTSUBSCRIPT italic_i italic_j end_POSTSUBSCRIPT = divide start_ARG italic_π - over^ start_ARG italic_φ end_ARG start_POSTSUBSCRIPT italic_i italic_j end_POSTSUBSCRIPT start_POSTSUPERSCRIPT italic_N italic_C end_POSTSUPERSCRIPT end_ARG start_ARG italic_N start_POSTSUBSCRIPT italic_Q italic_S , italic_j end_POSTSUBSCRIPT end_ARG . (11)

    phaselag (φ^ijNC<0{\rm phase\;lag}\mbox{ }(\hat{\varphi}_{ij}^{NC}<0roman_phase roman_lag ( over^ start_ARG italic_φ end_ARG start_POSTSUBSCRIPT italic_i italic_j end_POSTSUBSCRIPT start_POSTSUPERSCRIPT italic_N italic_C end_POSTSUPERSCRIPT < 0):

    aQ,j=1+sinϕij1sinϕij>1,ϕij=π+φ^ijNCNQS,j.formulae-sequencesubscript𝑎𝑄𝑗1subscriptitalic-ϕ𝑖𝑗1subscriptitalic-ϕ𝑖𝑗1subscriptitalic-ϕ𝑖𝑗𝜋superscriptsubscript^𝜑𝑖𝑗𝑁𝐶subscript𝑁𝑄𝑆𝑗a_{Q,j}=\frac{1+\sin\phi_{ij}}{1-\sin\phi_{ij}}>1,\;\phi_{ij}=\frac{\pi+\hat{% \varphi}_{ij}^{NC}}{N_{QS,j}}.italic_a start_POSTSUBSCRIPT italic_Q , italic_j end_POSTSUBSCRIPT = divide start_ARG 1 + roman_sin italic_ϕ start_POSTSUBSCRIPT italic_i italic_j end_POSTSUBSCRIPT end_ARG start_ARG 1 - roman_sin italic_ϕ start_POSTSUBSCRIPT italic_i italic_j end_POSTSUBSCRIPT end_ARG > 1 , italic_ϕ start_POSTSUBSCRIPT italic_i italic_j end_POSTSUBSCRIPT = divide start_ARG italic_π + over^ start_ARG italic_φ end_ARG start_POSTSUBSCRIPT italic_i italic_j end_POSTSUBSCRIPT start_POSTSUPERSCRIPT italic_N italic_C end_POSTSUPERSCRIPT end_ARG start_ARG italic_N start_POSTSUBSCRIPT italic_Q italic_S , italic_j end_POSTSUBSCRIPT end_ARG . (12)

    with φ^ijNC=(S^ijNC)superscriptsubscript^𝜑𝑖𝑗𝑁𝐶superscriptsubscript^𝑆𝑖𝑗𝑁𝐶\hat{\varphi}_{ij}^{NC}=\angle{(\hat{S}_{ij}^{NC})}over^ start_ARG italic_φ end_ARG start_POSTSUBSCRIPT italic_i italic_j end_POSTSUBSCRIPT start_POSTSUPERSCRIPT italic_N italic_C end_POSTSUPERSCRIPT = ∠ ( over^ start_ARG italic_S end_ARG start_POSTSUBSCRIPT italic_i italic_j end_POSTSUBSCRIPT start_POSTSUPERSCRIPT italic_N italic_C end_POSTSUPERSCRIPT ).

    Finally, the time constants of the lead/lag filter (TQ1,jsubscript𝑇𝑄1𝑗T_{Q1,j}italic_T start_POSTSUBSCRIPT italic_Q 1 , italic_j end_POSTSUBSCRIPT and TQ2,jsubscript𝑇𝑄2𝑗T_{Q2,j}italic_T start_POSTSUBSCRIPT italic_Q 2 , italic_j end_POSTSUBSCRIPT) are selected to achieve maximum lead/lag phase compensation at the frequency of the target electromechanical mode [44]:

    TQ1,j=1ωi0aQ,j, and TQ2,j=aQ,jTQ1,j.formulae-sequencesubscript𝑇𝑄1𝑗1superscriptsubscript𝜔𝑖0subscript𝑎𝑄𝑗 and subscript𝑇𝑄2𝑗subscript𝑎𝑄𝑗subscript𝑇𝑄1𝑗T_{Q1,j}=\frac{1}{\omega_{i}^{0}\sqrt{a_{Q,j}}},\mbox{ and }T_{Q2,j}=a_{Q,j}T% _{Q1,j}.italic_T start_POSTSUBSCRIPT italic_Q 1 , italic_j end_POSTSUBSCRIPT = divide start_ARG 1 end_ARG start_ARG italic_ω start_POSTSUBSCRIPT italic_i end_POSTSUBSCRIPT start_POSTSUPERSCRIPT 0 end_POSTSUPERSCRIPT square-root start_ARG italic_a start_POSTSUBSCRIPT italic_Q , italic_j end_POSTSUBSCRIPT end_ARG end_ARG , and italic_T start_POSTSUBSCRIPT italic_Q 2 , italic_j end_POSTSUBSCRIPT = italic_a start_POSTSUBSCRIPT italic_Q , italic_j end_POSTSUBSCRIPT italic_T start_POSTSUBSCRIPT italic_Q 1 , italic_j end_POSTSUBSCRIPT . (13)

    The resulting numerical eigenvalue sensitivity can be then calculated as:

    S^ij=S^ijNC[1+sTQ1,j1+saQ,jTQ1,j]s=λi0NQS,j=|S^ijNC|φ^ijsubscript^𝑆𝑖𝑗superscriptsubscript^𝑆𝑖𝑗𝑁𝐶superscriptsubscriptdelimited-[]1𝑠subscript𝑇𝑄1𝑗1𝑠subscript𝑎𝑄𝑗subscript𝑇𝑄1𝑗𝑠superscriptsubscript𝜆𝑖0subscript𝑁𝑄𝑆𝑗superscriptsubscript^𝑆𝑖𝑗𝑁𝐶subscript^𝜑𝑖𝑗\hat{S}_{ij}=\hat{S}_{ij}^{NC}\Big{[}\frac{1+sT_{Q1,j}}{1+sa_{Q,j}T_{Q1,j}}% \Big{]}_{s=\lambda_{i}^{0}}^{N_{QS,j}}=|\hat{S}_{ij}^{NC}|\angle{\hat{\varphi}% _{ij}}over^ start_ARG italic_S end_ARG start_POSTSUBSCRIPT italic_i italic_j end_POSTSUBSCRIPT = over^ start_ARG italic_S end_ARG start_POSTSUBSCRIPT italic_i italic_j end_POSTSUBSCRIPT start_POSTSUPERSCRIPT italic_N italic_C end_POSTSUPERSCRIPT [ divide start_ARG 1 + italic_s italic_T start_POSTSUBSCRIPT italic_Q 1 , italic_j end_POSTSUBSCRIPT end_ARG start_ARG 1 + italic_s italic_a start_POSTSUBSCRIPT italic_Q , italic_j end_POSTSUBSCRIPT italic_T start_POSTSUBSCRIPT italic_Q 1 , italic_j end_POSTSUBSCRIPT end_ARG ] start_POSTSUBSCRIPT italic_s = italic_λ start_POSTSUBSCRIPT italic_i end_POSTSUBSCRIPT start_POSTSUPERSCRIPT 0 end_POSTSUPERSCRIPT end_POSTSUBSCRIPT start_POSTSUPERSCRIPT italic_N start_POSTSUBSCRIPT italic_Q italic_S , italic_j end_POSTSUBSCRIPT end_POSTSUPERSCRIPT = | over^ start_ARG italic_S end_ARG start_POSTSUBSCRIPT italic_i italic_j end_POSTSUBSCRIPT start_POSTSUPERSCRIPT italic_N italic_C end_POSTSUPERSCRIPT | ∠ over^ start_ARG italic_φ end_ARG start_POSTSUBSCRIPT italic_i italic_j end_POSTSUBSCRIPT (14)
  2. 2.

    Calculation of the controller gain: Gain KQ,jsubscript𝐾𝑄𝑗K_{Q,j}italic_K start_POSTSUBSCRIPT italic_Q , italic_j end_POSTSUBSCRIPT is calculated to obtain the required dam** ratio of the target electromechanical mode:

    λidλi0+KQ,jS^ij.superscriptsubscript𝜆𝑖𝑑superscriptsubscript𝜆𝑖0subscript𝐾𝑄𝑗subscript^𝑆𝑖𝑗\lambda_{i}^{d}\approx\lambda_{i}^{0}+K_{Q,j}\hat{S}_{ij}.italic_λ start_POSTSUBSCRIPT italic_i end_POSTSUBSCRIPT start_POSTSUPERSCRIPT italic_d end_POSTSUPERSCRIPT ≈ italic_λ start_POSTSUBSCRIPT italic_i end_POSTSUBSCRIPT start_POSTSUPERSCRIPT 0 end_POSTSUPERSCRIPT + italic_K start_POSTSUBSCRIPT italic_Q , italic_j end_POSTSUBSCRIPT over^ start_ARG italic_S end_ARG start_POSTSUBSCRIPT italic_i italic_j end_POSTSUBSCRIPT . (15)
    KQ,j=γj|λidλi0||S^ij|subscript𝐾𝑄𝑗subscript𝛾𝑗superscriptsubscript𝜆𝑖𝑑superscriptsubscript𝜆𝑖0subscript^𝑆𝑖𝑗K_{Q,j}=\gamma_{j}\frac{|\lambda_{i}^{d}-\lambda_{i}^{0}|}{|\hat{S}_{ij}|}italic_K start_POSTSUBSCRIPT italic_Q , italic_j end_POSTSUBSCRIPT = italic_γ start_POSTSUBSCRIPT italic_j end_POSTSUBSCRIPT divide start_ARG | italic_λ start_POSTSUBSCRIPT italic_i end_POSTSUBSCRIPT start_POSTSUPERSCRIPT italic_d end_POSTSUPERSCRIPT - italic_λ start_POSTSUBSCRIPT italic_i end_POSTSUBSCRIPT start_POSTSUPERSCRIPT 0 end_POSTSUPERSCRIPT | end_ARG start_ARG | over^ start_ARG italic_S end_ARG start_POSTSUBSCRIPT italic_i italic_j end_POSTSUBSCRIPT | end_ARG (16)

    with KQ,j[KQ,jmax,KQ,jmax]subscript𝐾𝑄𝑗superscriptsubscript𝐾𝑄𝑗𝑚𝑎𝑥superscriptsubscript𝐾𝑄𝑗𝑚𝑎𝑥K_{Q,j}\in[-K_{Q,j}^{max},K_{Q,j}^{max}]italic_K start_POSTSUBSCRIPT italic_Q , italic_j end_POSTSUBSCRIPT ∈ [ - italic_K start_POSTSUBSCRIPT italic_Q , italic_j end_POSTSUBSCRIPT start_POSTSUPERSCRIPT italic_m italic_a italic_x end_POSTSUPERSCRIPT , italic_K start_POSTSUBSCRIPT italic_Q , italic_j end_POSTSUBSCRIPT start_POSTSUPERSCRIPT italic_m italic_a italic_x end_POSTSUPERSCRIPT ] and γj=1subscript𝛾𝑗1\gamma_{j}=1italic_γ start_POSTSUBSCRIPT italic_j end_POSTSUBSCRIPT = 1 if a positive gain is required and γj=1subscript𝛾𝑗1\gamma_{j}=-1italic_γ start_POSTSUBSCRIPT italic_j end_POSTSUBSCRIPT = - 1 if a negative gain is required.

IV Case study and results

Nordic 44 test system [45] is considered to analyse DC segmentation and the supplementary controllers described in Section III. Nordic 44 test system was initially implemented within iTesla project as an application example of the OpenIPSL library, implemented in the Modelica language [46, 47]. The version used in this paper is the one updated by the ALSETlab. The simulations will be carried out using the Dymola environment. OpenIPSL can be used for non-linear electromechanical time-domain simulation, and small-signal stability analysis. The information about the scenario considered is provided in Section V-A of the Appendix.

Initially, Nordic 44 test system is an AC power system. The starting point for the work presented in this paper is the architecture for DC-segmentation obtained by the algorithm for the mitigation of electromechanical oscillations proposed in [24], as shown in Fig. 6. VSC-HVDC link A has a rating of 3500 MVA, while VSC-HVDC link B has a rating of 800 MVA. Supplementary controllers for frequency support among the two AC areas (FC) and power-oscillation dam** for the intra-area modes by means of Q-modulation at the VSC stations (POD-Q controllers) will be analysed (see Section III).

Refer to caption
Figure 6: DC-segmented N44 test system under Dymola.

Four cases will be analysed and compared:

  • AC base case: The initial Nordic 44 test system. It corresponds to the case of Fig. 6 with AC lines instead of the DC links.

  • DCs constant PQ: The DC-segmented case without supplementary controllers.

  • DCs f-support, POD-Q-LF: The DC-segmented case with frequency support (FC) and POD-Q using local frequency (POD-Q-LF).

  • DCs f-support, POD-Q-FCOI: The DC-segmented case with frequency support (FC) and POD-Q using the frequency of the centre of inertia of each AC area (POD-Q-FCOI).

In the operating point, the power flows through the VSC-HVDC links is the same as the power flows through the AC lines of the base case: 447 MW and 1548 MW (from Region 1 to Region 2). The four cases have been compared by means of small-signal stability analysis (see Section IV-B) and non-linear time-domain simulations (see Section IV-C).

IV-A Design of POD-Q controllers

Table I presents the main modes of the Nordic 44 test system in the AC case and in the DC-segmented case without supplementary controllers. All the electromechanical modes with a dam** lower than 20% in at least one of the cases have been included. The table also indicates the location of each mode. Results show that the critical inter-area mode (mode 1), which has a low dam** ratio, has been mitigated with the DC-segmentation architecture obtained with the algorithm proposed in [24]. Nevertheless, there are still intra-area modes of each asynchronous AC area. POD-Q controllers (POD-Q-LF and POD-Q-FCOI described in Section III-B) will be used at every VSC station to increase the dam** ratio of some intra-area modes. POD-Q controllers will be designed following the methodology presented in Section III-C.

TABLE I: Poorly-damped electromechanical modes of the two initial cases.
AC base case DCs constant PQ Region of
N0. ζ𝜁\zetaitalic_ζ (%) Freq. (Hz) ζ𝜁\zetaitalic_ζ (%) Freq. (Hz) the mode
1 1.85 0.39 - - Inter-area
2 5.45 0.83 5.70 0.80 R1
3 11.68 0.88 11.92 0.87 R2
4 12.11 0.75 11.73 0.72 R2
5 - - 12.06 1.12 R2
6 12.12 1.07 12.14 1.07 R1
7 12.22 0.54 12.38 0.50 R2
8 13.12 0.98 13.12 0.95 R2
9 13.57 1.23 17.37 1.27 R1
10 15.69 1.10 14.81 1.12 R1

POD-Q controllers of VSCs of region 1 (ie. VSC-A1 or 5101 and VSC-B1 or 5100) will target mode 2 (with a dam** ratio of ζ=5.7𝜁5.7\zeta=5.7italic_ζ = 5.7 % and a frequency of 0.80 Hz) while the VSC of region 2 (ie. VSC-A2 or 3359 and VSC-B2 or 6500) will target mode 4 (with a dam** ratio of ζ=11.92𝜁11.92\zeta=11.92italic_ζ = 11.92 % and a frequency of 0.72 Hz). Each POD-Q controller will be designed independently to obtain a 15 % dam** for the targeted mode. Gain step used for the calculation of the numerical eigenvalue sensitivity is ΔKQ,j=20Δsubscript𝐾𝑄𝑗20\Delta K_{Q,j}=20roman_Δ italic_K start_POSTSUBSCRIPT italic_Q , italic_j end_POSTSUBSCRIPT = 20 pu (nominal pu). Pre-defined parameters of the POD-Q controllers are: TQf,j=0.1subscript𝑇𝑄𝑓𝑗0.1T_{Qf,j}=0.1italic_T start_POSTSUBSCRIPT italic_Q italic_f , italic_j end_POSTSUBSCRIPT = 0.1 s, TQW,j=5subscript𝑇𝑄𝑊𝑗5T_{QW,j}=5italic_T start_POSTSUBSCRIPT italic_Q italic_W , italic_j end_POSTSUBSCRIPT = 5 s, NQS,j=2subscript𝑁𝑄𝑆𝑗2N_{QS,j}=2italic_N start_POSTSUBSCRIPT italic_Q italic_S , italic_j end_POSTSUBSCRIPT = 2 and ±ΔQac,imax=±0.1plus-or-minusΔsuperscriptsubscript𝑄𝑎𝑐𝑖𝑚𝑎𝑥plus-or-minus0.1\pm\Delta Q_{ac,i}^{max}=\pm 0.1± roman_Δ italic_Q start_POSTSUBSCRIPT italic_a italic_c , italic_i end_POSTSUBSCRIPT start_POSTSUPERSCRIPT italic_m italic_a italic_x end_POSTSUPERSCRIPT = ± 0.1 pu. Maximum allowed POD-Q gain is set to KQ,jmax=±400superscriptsubscript𝐾𝑄𝑗𝑚𝑎𝑥plus-or-minus400K_{Q,j}^{max}=\pm 400italic_K start_POSTSUBSCRIPT italic_Q , italic_j end_POSTSUBSCRIPT start_POSTSUPERSCRIPT italic_m italic_a italic_x end_POSTSUPERSCRIPT = ± 400 pu.

Table II shows the parameters obtained for POD-Q-LF (local) and POD-Q-FCOI (global) controllers obatined with the design method of Section III-C. Notice that POD-Q gains reach their maximum allowed value. This is due to the fact that POD controllers in VSC-HVDC systems can be very effective if the VSC stations are well located to damp electromechanical oscillations [16]. However, POD-Q controllers in a DC-segmented system may not be in the best location to damp electromechanical oscillations. Precisely, the aim of this work is to analyse the capability of dam** intra-area electromechanical modes in DC-segmented system with a pre-defined scheme. It is also worth to highlight that some POD-Q gains have opposite signs, which is related to the location of the VSC stations in each AC area.

TABLE II: Parameters of the POD-Q controllers.
Case VSC KQ,jsubscript𝐾𝑄𝑗K_{Q,j}italic_K start_POSTSUBSCRIPT italic_Q , italic_j end_POSTSUBSCRIPT (pu) TQ1,jsubscript𝑇𝑄1𝑗T_{Q1,j}italic_T start_POSTSUBSCRIPT italic_Q 1 , italic_j end_POSTSUBSCRIPT (s) aQ,jsubscript𝑎𝑄𝑗a_{Q,j}italic_a start_POSTSUBSCRIPT italic_Q , italic_j end_POSTSUBSCRIPT
POD-Q-LF A1 (5101) -400 0.2847 0.486
B1 (5100) -400 0.2847 0.486
A2 (3359) 400 0.2223 0.999
B2 (6500) 400 0.2975 0.558
POD-Q-FCOI A1 (5101) -400 0.2750 0.521
B1 (5100) -400 0.2776 0.511
A2 (3359) 400 0.2402 0.856
B2 (6500) 400 0.2889 0.592

IV-B Small-signal stability analysis

Table III shows the main electromechanical modes of the system for the 4 cases.

TABLE III: Poorly-damped electromechanical modes of the four scenarios.
AC base case DCs constant PQ DCs f-support POD-Q-LF DCs f-support POD-Q-FCOI Region of
N0. ζ𝜁\zetaitalic_ζ (%) Freq. (Hz) ζ𝜁\zetaitalic_ζ (%) Freq. (Hz) ζ𝜁\zetaitalic_ζ (%) Freq. (Hz) ζ𝜁\zetaitalic_ζ (%) Freq. (Hz) the mode
1 1.85 0.39 - - - - - - Inter-area
2 5.45 0.83 5.70 0.80 11.53 0.84 12.40 0.83 R1
3 11.68 0.88 11.92 0.87 12.30 0.88 12.33 0.88 R2
4 12.11 0.75 11.73 0.72 15.52 0.74 15.40 0.74 R2
5 - - 12.06 1.12 12.44 1.10 12.16 1.07 R2
6 12.12 1.07 12.14 1.07 12.15 1.07 12.48 1.10 R1
7 12.22 0.54 12.38 0.50 15.02 0.48 16.45 0.47 R2
8 13.12 0.98 13.12 0.95 16.05 0.97 15.61 0.97 R2
9 13.57 1.23 17.37 1.27 20.68 1.31 20.68 1.31 R1
10 15.69 1.10 14.81 1.12 14.30 1.21 14.55 1.20 R1

Results show that:

  • The inter-area mode (mode 1 with a dam** ratio of 1.85 % and a frequency of 0.39 Hz) has been suppressed by the DC segmentation.

  • The main intra-area mode of region 1 (mode 2 with a dam** ratio of 5.7 % and a frequency of 0.8 Hz in the DC-segmented case without control) is well damped by the POD-Q controllers (+5.97 % with POD-Q-LF and +7.04 % with POD-Q-FCOI).

  • The main intra-area mode of region 2 (mode 4 with a dam** ratio of 11.73 % and a frequency of 0.72HZ in the DC-segmented case without control) is well damped by the POD-Q controllers (+3.62 % with POD-Q-LF and +3.67 % with POD-Q-FCOI).

  • Meanwhile, the dam** ratios of the rest of the electromechanical modes do not change significantly.

Notice that in the DC-segmented case, results obtained obtained with POD-Q-FCOI (global measurements) are slightly better than the ones obtained with POD-Q-LF (local measurements), although the improvements are similar. For this reason, taking into account that the implementation of POD-Q using local measurements is much easier, for this test system the use of POD-Q-LF seems to be a better solution than POD-Q-FCOI.

IV-C Non-linear time-domain simulation

IV-C1 Small perturbation


The disconnection of line 6001-5301 at Region 1 at t=1𝑡1t=1italic_t = 1 s (a small perturbation) has been simulated. The purpose of this simulation is to analyse electromechanical oscillations.

Fig. 7 shows the frequency of two representative generators (5600 in Region 1 and 7000 in Region 2) and Fig. 8 shows the Q injections of the VSCs of Region 1 after the disconnection of the line in Region 1. An poorly-damped inter-area oscillation can be clearly observed in AC base case, which corresponds to mode 1 of Table III (see Fig. 7). Results confirm the suppression of the inter-area mode in the 3 DC-segmented cases and the limitation of the first local mode of Region 1 (mode 2 of the Table III) in the two DC-segmented cases with both POD-Q-LF and POD-Q-FCOI. Furthermore, POD-Q-LF and POD-Q-FCOI controllers damp intra-area oscillations successfully (see Fig. 7) by means of reactive-power modulation (Fig. 8). Notice also that in the DC-segmented case with constant power control, the perturbation, that occurs at Region 1 is not propagated to Region 2 and, therefore, the frequency at buses in Region 2 remain constant to 50 Hz (see Fig. 7(b)). On the contrary, a small transient on the frequency at Region 2 is observed in the DC-segmented cases with supplementary controllers. This is due to the effect of the frequency controllers in the VSC-HVDC links.

Refer to caption
(a) Region 1
Refer to caption
(b) Region 2
Figure 7: Frequency of two representative generators after the disconnection of line 6001-5301 (Region 1).
Refer to caption
(a) VSC A1 (5100)
Refer to caption
(b) VSC B1 (5101)
Figure 8: Reactive power injection at the two VSC of Region 1 after the disconnection of line 6001-5301 (Region 1).

IV-C2 Disconnection of generator


The disconnection of a generator at bus 5300 (G5300-1 at Region 1) at t=1𝑡1t=1italic_t = 1 s has been simulated. This generator has a nominal power of 1200 MVA and it was injecting 723 MW before the event, and it is the one with highest active-power injection before the event. The purpose of this simulation is to analyse frequency stability.

Fig. 9 shows the frequency of the two representative generators used above after the disconnection of the generator in Region 1, while Fig. 10 shows the active power exchange between the two regions (from Region 1 to Region 2). In the AC base case, the frequency nadir and the final frequency are lower than the ones obtained in Region 1, because the two areas are connected synchronously through AC branches and the total frequency-support capability is greater. Naturally, in the AC base case the frequencies at regions 1 and 2 are in synchronism. In the DC segmented case with constant power control, the frequency nadir is low. This is because Region 1 only has frequency support from its synchronous generators and the VSC-HVDC links do not provide frequency support. Notice also that in the case of DC segmentation with constant power the frequency at Region 2 remains constant, because it is decoupled from Region 1 by the VSC-HVDC links. On the contrary in the DC-segmented cases with supplementary controllers, FC in the VSC-HVDC links produces frequency support among the two regions. This causes the frequency nadir to be higher than the one obtained in the DC-segmented case with constant power. The effects of frequency support through the VSC-HVDC links can be observed in Fig. 10, where they reduce the power exchange between Region 1 and 2. As a consequence, in the DC-segmented cases with supplementary controllers, the frequency at Region 2 also changes, due to the effect of FC controllers in the VSC-HVDC links.

Table IV shows the frequency nadir (fminsubscript𝑓𝑚𝑖𝑛f_{min}italic_f start_POSTSUBSCRIPT italic_m italic_i italic_n end_POSTSUBSCRIPT) and final steady-state frequency (ffinalsubscript𝑓𝑓𝑖𝑛𝑎𝑙f_{final}italic_f start_POSTSUBSCRIPT italic_f italic_i italic_n italic_a italic_l end_POSTSUBSCRIPT) after the disconnection of generator G5300-1 in Region 1. Note that the results of the table may not correspond exactly to the ones of Fig. 9 for the final frequency since the steady state has not been reached in the figure. Results for the disconnection of a generator in Region 2 are also included in the table (G3300-1), which has a nominal power of 1100 MVA and it was injecting 757 MW before the event. As a conclusion, in the DC-segmented cases with supplementary controllers, overall frequency stability is improved, in comparison with the DC-segmented case with constant power.

Additionally, DC segmentation with and without frequency support significantly reduces the change of power flow in the inter area link (see Fig. 10). This could avoid trip** of the line in cases where the link is close to its maximum capacity, this could be of interest in cases in where this aspect is critical.

TABLE IV: Frequency Nadir and steady state after a disconnection of generator in Region 1 or 2 in the four cases.
Disconnection Frequency (Hz) AC case DCs constant DCs f-support DCs f-support
of generator in: PQ POD-Q-LF POD-Q-FCOI
Region 1 fminsubscript𝑓𝑚𝑖𝑛f_{min}italic_f start_POSTSUBSCRIPT italic_m italic_i italic_n end_POSTSUBSCRIPT (Hz) 49.85 49.68 49.74 49.75
ffinalsubscript𝑓𝑓𝑖𝑛𝑎𝑙f_{final}italic_f start_POSTSUBSCRIPT italic_f italic_i italic_n italic_a italic_l end_POSTSUBSCRIPT (Hz) 49.97 49.94 49.94 49.94
Region 2 fminsubscript𝑓𝑚𝑖𝑛f_{min}italic_f start_POSTSUBSCRIPT italic_m italic_i italic_n end_POSTSUBSCRIPT (Hz) 49.86 49.76 49.79 49.79
ffinalsubscript𝑓𝑓𝑖𝑛𝑎𝑙f_{final}italic_f start_POSTSUBSCRIPT italic_f italic_i italic_n italic_a italic_l end_POSTSUBSCRIPT (Hz) 49.97 49.93 49.94 49.94
Refer to caption
(a) Region 1
Refer to caption
(b) Region 2
Figure 9: Frequency of two representative generators after the disconnection of a generator at bus 5300 (Region 1).
Refer to caption
(a) Link A (5100-6500)
Refer to caption
(b) Link B (5101-3359)
Figure 10: Active power exchange from region 1 to region 2 after the disconnection of a generator at bus 5300 (Region 1).

IV-D Impact of communication latency

The implementation of the POD-Q-FCOI requires a communication system between the generators and the VSCs and its impact on the performance of the controller is analysed here.

A central control scheme is assumed, where the input error signal of POD-Q-FCOI of Fig. 4 with a communication delay reads:

ui=esτ(ωCOI,iωi)subscript𝑢𝑖superscript𝑒𝑠𝜏subscript𝜔𝐶𝑂𝐼𝑖subscript𝜔𝑖u_{i}=e^{-s\tau}(\omega_{COI,i}-\omega_{i})italic_u start_POSTSUBSCRIPT italic_i end_POSTSUBSCRIPT = italic_e start_POSTSUPERSCRIPT - italic_s italic_τ end_POSTSUPERSCRIPT ( italic_ω start_POSTSUBSCRIPT italic_C italic_O italic_I , italic_i end_POSTSUBSCRIPT - italic_ω start_POSTSUBSCRIPT italic_i end_POSTSUBSCRIPT ) (17)

where τ𝜏\tauitalic_τ is the total communication delay.

The delay of (17) has been implemented using a first-order Padé’s approximation. Realistic values of communication latency delays are analysed (τ=50𝜏50\tau=50italic_τ = 50 ms and τ=100𝜏100\tau=100italic_τ = 100 ms).

Table V shows the main electromechanical modes of the system for DCs f-support POD-Q-FCOI for different values of communication latency delays. The modes considered are the same as the ones of Table III. Results show that the communication delays slightly reduce the dam** ratio of the target modes (from 12.40% to 9.95% for mode 2 and from 15.40% to 14.37% for a delay τ=0.1s𝜏0.1𝑠\tau=0.1sitalic_τ = 0.1 italic_s) without significant impact on other modes. Therefore, results prove that POD-Q-FCOI controller is robust against communication latency. Independently of this, as previously discussed, since POD-Q-LF controller uses local signals and both controllers produce similar results, POD-Q-LF controller appears to be a best alternative than POD-Q-FCOI controller, for the test system used in this work.

TABLE V: Poorly-damped electromechanical modes of the DCs f-support, POD-Q-FCOI with various communication delays.
No delay τ𝜏\tauitalic_τ = 0.05s τ𝜏\tauitalic_τ = 0.1s Region of
N0. ζ𝜁\zetaitalic_ζ (%) Freq. (Hz) ζ𝜁\zetaitalic_ζ (%) Freq. (Hz) ζ𝜁\zetaitalic_ζ (%) Freq. (Hz) the mode
2 12.40 0.83 11.14 0.84 9.95 0.84 R1
3 12.33 0.88 12.19 0.88 12.04 0.88 R2
4 15.40 0.74 14.86 0.74 14.37 0.75 R2
5 12.16 1.07 12.19 1.07 12.22 1.07 R2
6 12.48 1.10 12.65 1.10 12.79 1.10 R1
7 16.45 0.47 17.41 0.48 18.28 0.48 R2
8 15.61 0.97 15.10 0.98 14.11 0.99 R2
9 20.68 1.31 20.68 1.31 20.68 1.31 R1
10 14.55 1.20 13.84 1.20 13.18 1.19 R1

V Conclusions

The conclusions obtained in this work can be summarised as follows:

  • DC segmentation can be very effective to suppress critical inter-area oscillation in stressed AC power systems. However, if VSC-HVDC systems are controlled with constant power: (a) overall frequency stability will be jeopardised, because each asynchronous AC cluster will have lower amounts of frequency support and inertia and (b) intra-area electromechanical oscillations in the AC clusters may have similar dam** ratio to those obtained in the AC base case, with room for further improvement.

  • Frequency controllers (FC) in the VSC-HVDC links of a DC-segmented system allows frequency support among the different AC clusters, improving overall frequency stability, in comparison with DC segmentation with constant power control.

  • Power oscillation dam** controllers for the reactive-power injections (POD-Q) in the VSC-HVDC links of a DC-segmented system can be used to damp intra-area oscillations of the asynchronous AC clusters, in addition to the mitigation of the critical inter-area oscillation due to DC segmentation. Two effective POD-Q controllers were analysed and compared: POD-Q-LF (using local measurements), based on previous proposals and POD-Q-FCOI (using global measurements), proposed in this work.

  • POD-Q-LF (local) and POD-Q-FCOI (global) controllers produced comparable results, and the latter proved to be robust when subject to communication latencies. Nevertheless, taking into account that implementation of POD controllers using remote signals is more complex and expensive than POD controllers using local signals, POD-Q-LF controller seems to be a more practical solution than POD-Q-FCOI controller, for the test system considered.

  • The concept of numerical eigenvalue sensitivity is proposed and used for the design of POD-Q controllers in the DC-segmented power system, which is an approximation of the theoretical eigenvalue sensitivity and can facilitate its implementation in small-signal-stability tools with limited information of the state matrices. Hence, it has a practical application that could be used for the design of POD controllers in general, and not only in DC-segmented power systems.

  • The use of DC segmentation, frequency support and POD-Q control brought an important improvement of the overall stability of the test system compared to the initial AC case.

Appendix

V-A AC base case

Dynamic and static data of the Nordic 44 test system can be found under [48]. The initial power flow condition used in this paper correspond to the Nord Pool data of Tuesday November 10 at 11:38 available at the same link.

V-B DC-segmented cases

The DC-segmented cases were obtained from the initial Nordic 44 system by replacing AC line 5100-6500 (link B) and the two parallel lines between buses 3359 and 5101 (link A) with VSC-HVDC links. The characteristics of the four VSCs and the two DC lines are included in Table VI.

TABLE VI: Data of the HVDC links in the DC-segmented Nordic 44 system.
Parameters
(p.u’s: converter rating) Values
Rating VSC (VSCA1-2/ VSCB1-2) 3500/800 MVA
DC voltage (VSCA1-2/ VSCB1-2) ±plus-or-minus\pm± 535/320 kV
Configuration Symmetrical monopole
Max active power (VSCA1-2/ VSCB1-2) ±3500/800MWplus-or-minus3500800𝑀𝑊\pm 3500/800MW± 3500 / 800 italic_M italic_W
Max reactive power (VSCA1-2/ VSCB1-2) ±1400/320MVArplus-or-minus1400320𝑀𝑉𝐴𝑟\pm 1400/320MVAr± 1400 / 320 italic_M italic_V italic_A italic_r
Max. current 1 p.u.
Max. DC voltage Vdc,imax,Vdc,iminsubscriptsuperscript𝑉𝑚𝑎𝑥𝑑𝑐𝑖subscriptsuperscript𝑉𝑚𝑖𝑛𝑑𝑐𝑖V^{max}_{dc,i},V^{min}_{dc,i}italic_V start_POSTSUPERSCRIPT italic_m italic_a italic_x end_POSTSUPERSCRIPT start_POSTSUBSCRIPT italic_d italic_c , italic_i end_POSTSUBSCRIPT , italic_V start_POSTSUPERSCRIPT italic_m italic_i italic_n end_POSTSUPERSCRIPT start_POSTSUBSCRIPT italic_d italic_c , italic_i end_POSTSUBSCRIPT 1.1, 0.9 p.u.
Current-controller time constant (τ𝜏\tauitalic_τ) 2 ms
Connection imp. (Rs,i+jXs,isubscript𝑅𝑠𝑖𝑗subscript𝑋𝑠𝑖R_{s,i}+jX_{s,i}italic_R start_POSTSUBSCRIPT italic_s , italic_i end_POSTSUBSCRIPT + italic_j italic_X start_POSTSUBSCRIPT italic_s , italic_i end_POSTSUBSCRIPT) 0.004 + j 0.2 p.u.
Outer control gains
P control iac,d,iref=Pac,i/Vac,isuperscriptsubscript𝑖𝑎𝑐𝑑𝑖𝑟𝑒𝑓superscriptsubscript𝑃𝑎𝑐𝑖subscript𝑉𝑎𝑐𝑖i_{ac,d,i}^{ref}=P_{ac,i}^{*}/V_{ac,i}italic_i start_POSTSUBSCRIPT italic_a italic_c , italic_d , italic_i end_POSTSUBSCRIPT start_POSTSUPERSCRIPT italic_r italic_e italic_f end_POSTSUPERSCRIPT = italic_P start_POSTSUBSCRIPT italic_a italic_c , italic_i end_POSTSUBSCRIPT start_POSTSUPERSCRIPT ∗ end_POSTSUPERSCRIPT / italic_V start_POSTSUBSCRIPT italic_a italic_c , italic_i end_POSTSUBSCRIPT
Vdc prop./int.(Kp,d2/Ki,d2subscript𝐾𝑝𝑑2subscript𝐾𝑖𝑑2K_{p,d2}/K_{i,d2}italic_K start_POSTSUBSCRIPT italic_p , italic_d 2 end_POSTSUBSCRIPT / italic_K start_POSTSUBSCRIPT italic_i , italic_d 2 end_POSTSUBSCRIPT) 10 p.u./20 p.u./s
Q control iac,q,iref=Qac,i/Vac,isuperscriptsubscript𝑖𝑎𝑐𝑞𝑖𝑟𝑒𝑓superscriptsubscript𝑄𝑎𝑐𝑖subscript𝑉𝑎𝑐𝑖i_{ac,q,i}^{ref}=-Q_{ac,i}^{*}/V_{ac,i}italic_i start_POSTSUBSCRIPT italic_a italic_c , italic_q , italic_i end_POSTSUBSCRIPT start_POSTSUPERSCRIPT italic_r italic_e italic_f end_POSTSUPERSCRIPT = - italic_Q start_POSTSUBSCRIPT italic_a italic_c , italic_i end_POSTSUBSCRIPT start_POSTSUPERSCRIPT ∗ end_POSTSUPERSCRIPT / italic_V start_POSTSUBSCRIPT italic_a italic_c , italic_i end_POSTSUBSCRIPT
VSCs’ loss coefficients a = b = c = 0 p.u.
DC-bus capacitance (Cdc,isubscript𝐶𝑑𝑐𝑖C_{dc,i}italic_C start_POSTSUBSCRIPT italic_d italic_c , italic_i end_POSTSUBSCRIPT) (VSCA1-2/ VSCB1-2) 305/195 μF𝜇𝐹\mu Fitalic_μ italic_F
DC-line series resistance, inductance (Rdc,ij,Ldc,ijsubscript𝑅𝑑𝑐𝑖𝑗subscript𝐿𝑑𝑐𝑖𝑗R_{dc,ij},L_{dc,ij}italic_R start_POSTSUBSCRIPT italic_d italic_c , italic_i italic_j end_POSTSUBSCRIPT , italic_L start_POSTSUBSCRIPT italic_d italic_c , italic_i italic_j end_POSTSUBSCRIPT)
- link A (5101-3359) 1.6 ΩΩ\Omegaroman_Ω, 67 mH
- line B (5100-6500) 7.2 ΩΩ\Omegaroman_Ω, 258 mH

VSCs A2 (3359) and B2 (6500) were set in Vdcsubscript𝑉𝑑𝑐V_{dc}italic_V start_POSTSUBSCRIPT italic_d italic_c end_POSTSUBSCRIPT-control mode while VSCs A1 (5101) and B1 (5100) were set in P𝑃Pitalic_P-control mode.

Parameters of Frequency Controller (FC) (Fig. 3 of Section III-A) are KFC,i=100subscript𝐾𝐹𝐶𝑖100K_{FC,i}=100italic_K start_POSTSUBSCRIPT italic_F italic_C , italic_i end_POSTSUBSCRIPT = 100 pu, TFC,i=0.1subscript𝑇𝐹𝐶𝑖0.1T_{FC,i}=0.1italic_T start_POSTSUBSCRIPT italic_F italic_C , italic_i end_POSTSUBSCRIPT = 0.1 s and ±ΔPac,imax=±1plus-or-minusΔsuperscriptsubscript𝑃𝑎𝑐𝑖𝑚𝑎𝑥plus-or-minus1\pm\Delta P_{ac,i}^{max}=\pm 1± roman_Δ italic_P start_POSTSUBSCRIPT italic_a italic_c , italic_i end_POSTSUBSCRIPT start_POSTSUPERSCRIPT italic_m italic_a italic_x end_POSTSUPERSCRIPT = ± 1 pu.

Acknowledgments

The work of Mr. Mathieu Robin is within a collaboration of SuperGrid institute in the doctoral programme of Comillas Pontifical University.

References

  • [1] B. Luscan, S. Bacha, A. Benchaib, A. Bertinato, L. Chedot, J. C. Gonzalez-Torres, S. Poullain, M. Romero-Rodriguez, and K. Shinoda, “A Vision of HVDC Key Role Toward Fault-Tolerant and Stable AC/DC Grids,” IEEE Journal of Emerging and Selected Topics in Power Electronics, vol. 9, no. 6, pp. 7471–7485, Dec. 2021.
  • [2] ENTSO-E, “Grid Map,” https://www.entsoe.eu/data/map/, Feb. 2023.
  • [3] A. Alassi, S. Bañales, O. Ellabban, G. Adam, and C. MacIver, “HVDC Transmission: Technology Review, Market Trends and Future Outlook,” Renewable and Sustainable Energy Reviews, vol. 112, pp. 530–554, Sep. 2019.
  • [4] O. Gomis-Bellmunt, E. Sanchez-Sanchez, J. Arevalo-Soler, and E. Prieto-Araujo, “Principles of operation of grids of DC and AC subgrids interconnected by power converters,” IEEE Transactions on Power Delivery, vol. 36, no. 2, pp. 1107–1117, Apr. 2021.
  • [5] ENTSO-E, “Analysis of CE Inter-Area Oscillations of 1st December 2016,” ENTSO-E, Brussels, Belgium, SG SPD REPORT, 2017.
  • [6] N. Hatziargyriou, J. Milanovic, C. Rahmann, V. Ajjarapu, C. Canizares, I. Erlich, D. Hill, I. Hiskens, I. Kamwa, B. Pal, P. Pourbeik, J. Sanchez-Gasca, A. Stankovic, T. Van Cutsem, V. Vittal, and C. Vournas, “Definition and Classification of Power System Stability – Revisited & Extended,” IEEE Transactions on Power Systems, vol. 36, no. 4, pp. 3271–3281, Jul. 2021.
  • [7] M. Klein, G. J. Rogers, and P. Kundur, “A fundamental study of inter-area oscillations in power systems,” IEEE Transactions on Power Systems, vol. 6, no. 3, pp. 914–921, Aug./1991.
  • [8] J. L. Domínguez-García, O. Gomis-Bellmunt, F. D. Bianchi, and A. Sumper, “Power oscillationg dam** supported by wind power: A review,” Renewable and Sustainable Energy Reviews, vol. 16, no. 1, pp. 4994–5006, 2012.
  • [9] R. Shah, N. Mithulananthan, and K. Y. Lee, “Large-Scale PV Plant With a Robust Controller Considering Power Oscillation Dam**,” IEEE Transactions on Energy Conversion, vol. 28, no. 1, pp. 106–116, 2013.
  • [10] J. Jankovic, J. Roldan-Perez, M. Prodanovic, J. A. Suul, S. D’Arco, and L. Rouco-Rodriguez, “Power oscillation dam** method suitable for network reconfigurations based on converter interfaced generation and combined use of active and reactive powers,” International Journal of Electrical Power and Energy Systems, vol. 149, no. 109010, pp. 1–10, 2023.
  • [11] L. Rouco, “Coordinated design of multiple controllers for dam** power system oscillations,” International Journal of Electrical Power & Energy Systems, vol. 23, no. 7, pp. 517–530, Oct. 2001.
  • [12] N. Mithulanathan, C. A. Canizares, J. Reeve, and G. J. Rogers, “Comparison of PSS, SVC and STATCOM controllers for dam** power system oscillations,” IEEE Transactions on Power Systems, vol. 18, no. 2, pp. 786–792, 2003.
  • [13] B. J. Pierre, F. Wilches-Bernal, D. A. Schoenwald, R. T. Elliott, D. J. Trudnowski, R. H. Byrne, and J. C. Neely, “Design of the Pacific Intertie Wide Area Dam** Controller,” IEEE Transactions on Power Systems, vol. 34, no. 5, pp. 3594–3604, 2017.
  • [14] R. Eriksson, “A New Control Structure for Multiterminal DC Grids to Damp Interarea Oscillations,” IEEE Transactions on Power Delivery, vol. 31, no. 3, pp. 990–998, Jun. 2016.
  • [15] M. A. Elizondo, R. Fan, H. Kirkham, M. Ghosal, F. Wilches-Bernal, D. Schoenwald, and J. Lian, “Interarea Oscillation Dam** Control Using High-Voltage DC Transmission: A Survey,” IEEE Transactions on Power Systems, vol. 33, no. 6, pp. 6915–6923, Nov. 2018.
  • [16] J. Renedo, A. Garcia-Cerrada, L. Rouco, and L. Sigrist, “Coordinated Design of Supplementary Controllers in VSC-HVDC Multi-Terminal Systems to Damp Electromechanical Oscillations,” IEEE Transactions on Power Systems, vol. 36, no. 1, pp. 712–721, Jan. 2021.
  • [17] J. Gonzalez-Torres, J. Mermet-Guyennet, S. Silvant, and A. Benchaib, “Power system stability enhancement via VSC-HVDC control using remote signals: Application on the Nordic 44-bus test system,” in 15th IET International Conference on AC and DC Power Transmission (ACDC), Coventry, UK, 2019, pp. 1–6.
  • [18] Y. Xing, E. Kamal, B. Marinescu, and F. Xavier, “Advanced control to damp power oscillations with VSC‐HVDC links inserted in meshed AC grids,” International Transactions on Electrical Energy Systems, vol. 31, no. 12, pp. 1–26, 2021.
  • [19] Y. Dong, Y. Zhao, K. Alshuaibi, C. Zhang, Y. Liu, L. Zhu, E. Farantatos, K. Sun, B. Marshall, M. Rahman, O. Adeuyi, S. Marshall, and I. L. Cowan, “Adaptive Power Oscillation Dam** Control via VSC- HVDC for the Great Britain Power Grid,” in 2023 IEEE Power & Energy Society Innovative Smart Grid Technologies Conference (ISGT).   Washington, DC, USA: IEEE, Jan. 2023, pp. 1–5.
  • [20] J. Li, C.-C. Liu, and K. P. Schneider, “Controlled Partitioning of a Power Network Considering Real and Reactive Power Balance,” IEEE Transactions on Smart Grid, vol. 1, no. 3, pp. 261–269, Dec. 2010.
  • [21] A. R. Hassani Ahangar, G. B. Gharehpetian, and H. R. Baghaee, “A review on intentional controlled islanding in smart power systems and generalized framework for ICI in microgrids,” International Journal of Electrical Power & Energy Systems, vol. 118, p. 105709, Jun. 2020.
  • [22] H. You, V. Vittal, and X. Wang, “Slow Coherency-Based Islanding,” IEEE Transactions on Power Systems, vol. 19, no. 1, pp. 483–491, Feb. 2004.
  • [23] Kai Sun, Da-Zhong Zheng, and Qiang Lu, “Splitting strategies for islanding operation of large-scale power systems using OBDD-based methods,” IEEE Transactions on Power Systems, vol. 18, no. 2, pp. 912–923, May 2003.
  • [24] M. Robin, J. Renedo, J. C. Gonzalez-Torres, A. Garcia-Cerrada, A. Benchaib, and P. Garcia-Gonzalez, “An Algorithm for DC Segmentation of AC Power Systems to Mitigate Electromechanical Oscillations,” IEEE Access, vol. 11, pp. 64 651–64 667, 2023.
  • [25] H. K. Clark, M. M. El-Gasseir, H. D. Kenneth Epp, and A.-A. Edris, “The application of segmentation and grid shock absorber concept for reliable power grids,” in 2008 12th International Middle-East Power System Conference.   Aswan, Egypt: IEEE, Mar. 2008, pp. 34–38.
  • [26] ENTSO-E, “HVDC Links in System Operations,” ENTSO-E, Brussels, Belgium, Technical Paper, Dec. 2019.
  • [27] P. Fairley, “Why Southern China broke up its power grid,” IEEE SPECTRUM, pp. 13–14, Dec. 2016.
  • [28] H. Clark, A.-A. Edris, M. El-Gasseir, K. Epp, A. Isaacs, and D. Woodford, “Softening the blow of disturbance,” IEEE power & energy magazine, vol. vol. 6, no. no. 1, pp. 30–41, 2008.
  • [29] X. Fang and J. H. Chow, “BTB DC link modeling, control, and application in the segmentation of AC interconnections,” in 2009 IEEE Power & Energy Society General Meeting.   Calgary, Canada: IEEE, Jul. 2009, pp. 1–7.
  • [30] U. T. Shami, R. Naeem, and M. S. Chaudhary, “Analysis of Different Power Grid Segmentation and Transmission Schemes for Power System Security Improvement,” University of Engineering and Technology Taxila. Technical Journal, vol. 20, no. I, pp. 39–49, 2015.
  • [31] O. A. Mousavi, L. Bizumic, and R. Cherkaoui, “Assessment of HVDC grid segmentation for reducing the risk of cascading outages and blackouts,” in 2013 IREP Symposium Bulk Power System Dynamics and Control - IX Optimization, Security and Control of the Emerging Power Grid.   Rethymno, Greece: IEEE, Aug. 2013, pp. 1–10.
  • [32] D. Gomila, B. Carreras, J. Reynolds-Barredo, P. Colet, and O. Gomis-Bellmunt, “Analysis of the blackout risk reduction when segmenting large power systems using lines with controllable power flow,” International Journal of Electrical Power & Energy Systems, vol. 148, p. 108947, Jun. 2023.
  • [33] O. Stanojev, J. Garrison, S. Hedtke, C. M. Franck, and T. Demiray, “Benefit Analysis of a Hybrid HVAC/HVDC Transmission Line: A Swiss Case Study,” in 2019 IEEE Milan PowerTech.   Milan, Italy: IEEE, Jun. 2019, pp. 1–6.
  • [34] D. Hart, A. Xemard, S. Poullain, Z. Rubinic, T. Dolenc, K. Pavic, I. Uglesic, V. Milardic, G. Levacic, and M. Mesic, “Transformation of an AC transmission line into a DC transmission line: A study case,” in CIGRE International Symposium 2021 ”Resha** the Electric Power System Infrastructure”.   Ljubljana: CIGRE, Jun. 2021, pp. 1–17.
  • [35] M. Robin, J. Renedo, J.-C. Gonzalez-Torres, A. Garcia-Cerrada, A. Benchaib, and P. Garcia-Gonzalez, “DC segmentation: A promising solution to improve angle stability of stressed power systems,” in The 17th International Conference on AC and DC Power Transmission (ACDC 2021), Online Conference, 2021, pp. 84–90.
  • [36] L. M. Castro and E. Acha, “On the Provision of Frequency Regulation in Low Inertia AC Grids Using HVDC Systems,” IEEE Transactions on Smart Grid, vol. 7, no. 6, pp. 2680–2690, Nov. 2016.
  • [37] Q. Zhang, J. D. McCalley, V. Ajjarapu, J. Renedo, M. A. Elizondo, A. Tbaileh, and N. Mohan, “Primary Frequency Support Through North American Continental HVDC Interconnections With VSC-MTDC Systems,” IEEE Transactions on Power Systems, vol. 36, no. 1, pp. 806–817, Jan. 2021.
  • [38] K. Shinoda, J. Dai, G. Bakhos, J. C. Gonzalez-Torres, A. Benchaib, and S. Bacha, “Design consideration for frequency containment reserve provisions by a multi-terminal hvdc system,” IET Generation, Transmission and Distribution, vol. 17, pp. 4024––4037, 2023.
  • [39] Y. Chompoobutrgool and L. Vanfretti, “Identification of Power System Dominant Inter-Area Oscillation Paths,” IEEE Transactions on Power Systems, vol. 28, no. 3, pp. 2798–2807, Aug. 2013.
  • [40] S. Cole, J. Beerten, and R. Belmans, “Generalized Dynamic VSC MTDC Model for Power System Stability Studies,” IEEE Transactions on Power Systems, vol. 25, no. 3, pp. 1655–1662, Aug. 2010.
  • [41] L. Rouco, F. L. Pagola, A. Garcia-Cerrada, J. M. Rodriguez, and R. M. Sanz, “Dam** of electromechanical oscillations in power systems with superconduction magnetic energy storage systems: Location and controller design,” in 12th Power Systems Computation Conference, vol. 1097–1104, Dresden, Aug. 1996.
  • [42] L. Díez-Maroto, J. Renedo, L. Rouco, and F. Fernández-Bernal, “Lyapunov Stability Based Wide Area Control Systems for Excitation Boosters in Synchronous Generators,” IEEE Transactions on Power Systems, vol. 34, no. 1, pp. 194–204, 2019.
  • [43] F. Pagola, I. J. Perez-Arriaga, and G. Verghese, “On sensitivities, residues and participations: Applications to oscillatory stability analysis and control,” IEEE Transactions on Power Systems, vol. 4, no. 1, pp. 278–285, Feb. 1989.
  • [44] E. V. Larsen and D. A. Swann, “Applying Power System Stabilizers Part II: Performance Objectives and Tuning Concepts,” IEEE Transactions on Power Apparatus and Systems, vol. PAS-100, no. 6, pp. 3025–3033, 1981.
  • [45] S. H. Jakobsen, L. Kalemba, and E. H. Solvang, “The Nordic 44 test Network,” Online: https://figshare. com/projects/Nordic\_44/57905, p. 1001438 Bytes, 2018.
  • [46] L. Vanfretti, T. Rabuzin, M. Baudette, and M. Murad, “iTesla Power Systems Library (iPSL): A Modelica library for phasor time-domain simulations,” SoftwareX, vol. 5, pp. 84–88, 2016.
  • [47] M. Baudette, M. Castro, T. Rabuzin, J. Lavenius, T. Bogodorova, and L. Vanfretti, “OpenIPSL: Open-Instance Power System Library — Update 1.5 to “iTesla Power Systems Library (iPSL): A Modelica library for phasor time-domain simulations”,” SoftwareX, vol. 7, pp. 34–36, Jan. 2018.
  • [48] “Nordic44-Nordpool/N44_BC.dyr at master \cdot ALSETLab/Nordic44-Nordpool,” https://github.com/ALSETLab/Nordic44-Nordpool, Oct. 2022.

Mathieu Robin obtained the M.Eng degree from Ecole Centrale Lyon, Ecully, France and the M.Sc degree in Electrical Engineering from jointly Ecole Centrale Lyon and Claude Bernard University in Lyon, France, both in 2019. He is actually pursuing his Ph.D. degree at Universidad Pontificia Comillas de Madrid (UPCO), Madrid, Spain and is working as a research engineer at SuperGrid Institute, Villeurbanne, France.

His research interests are stability, modelling and control of power systems, particularly VSC-HVDC systems and DC segmentation.

Javier Renedo (Senior Member, IEEE) received his M.Sc. degree in electrical engineering from Universidad Pontificia Comillas de Madrid (Comillas, for short), Spain, in 2010, the M.Sc. degree in mathematical engineering from Universidad Carlos III de Madrid, Spain, in 2013, and the Ph.D. degree in modelling of engineering systems from Comillas, in 2018. His research interests include power system stability, VSC-HVDC systems, and power systems with large amounts of renewable resources.

Juan Carlos Gonzalez Torres received both the Electromechanical Engineering degree from Universidad Autonoma de San Luis Potosi and the Master of Engineering from Ecole Centrale de Lille in 2014. He graduated with a Master of Science degree from ParisTech (The Paris Institute of Technology) in 2015. In 2019, he obtained the Ph.D. in Automatic Control from Paris-Saclay University. He has been working as a research engineer at Supergrid Institute since 2016, where he is part of the Architecture & Systems program. His main research interests include modeling and control of power systems, HVDC transmission systems and integration of renewable energies via power electronics-based devices.

Aurelio Garcia Cerrada (Senior Member, IEEE from 2015) M.Sc. (1986) from the Universidad Politécnica de Madrid, Spain, and Ph.D. (1991) from the University of Birmingham, U.K. He is a Professor in the Electronics, Control Engineering and Communications Department and a member of the Institute for Research in Technology (IIT) at the Universidad Pontificia Comillas de Madrid. His research focuses on power electronics and its applications to electric energy systems.

Luis Rouco (Senior Member, IEEE) received the “Ingeniero Industrial and “Doctor Ingeniero Industrial degrees from Universidad Politécnica de Madrid in 1985 and 1990 respectively. He is Professor of electrical engineering with the Department of Electrical Engineering of the School of Engineering of Universidad Pontificia Comillas. He served as Head of the Department from 1999 through 2005. He develops his research activities at Instituto de Investigación Tecnológica (IIT). Prof. Rouco is a Distinguished Member of Cigré and Member of the Executive Committee of Spanish National Committee of Cigré. He has been Visiting Scientist at Ontario Hydro, MIT and ABB Power Systems.

Abdelkrim Benchaib received his Ph.D. from the Automatic Systems Laboratory, Picardie University, France, in December 1998 and in 2014 his HDR (French postdoctoral degree allowing its holder to supervise PhD students) from Paris-Orsay University. He joined Alstom in July 2000 where he has been working as a power quality and smart grid project leader and thereafter with GE Grid solutions. Currently, he is seconded by GE to work with the SuperGrid institute where he is a Sub-program group leader for real-time strategies of super grids AC/DC control and dispatch. His expertise and research interests include automatic control, AC and DC power systems and power electronics. Dr. Benchaib is associate Professor at the Cnam (Conservatoire National des Arts et Metiers) teaching wind energy and power network. He has been General Chairman of the EPE ECCE Europe Conference for its 2020 edition (EPE conference is one of the bigest events in the world for Power Electronics with up to 1000 participants) . Abdelkrim Benchaib is the secretary of the EPE association.

Pablo Garcia Gonzalez holds a M.Sc. in electrical engineering (1992) and a PhD (2000), both from the Universidad Pontificia Comillas, Madrid, Spain. He is a Full Professor at the ICAI School of Engineering. His teaching and research activities focus on applications of power electronics, control systems, and the integration of distributed energy resources in power systems.