On the dam** of power systems during inverter-based blackstart
Authors:
Adolfo Anta,
Diego Cifelli
Abstract:
The massive deployment of inverter-based generation poses several challenges to system operators but also offers new opportunities. In the context of grid recovery, inverter-based generation is expected to take over new responsibilities, as conventional generation that are blackstart capable are being decommissioned. Inverter-based facilities, being very flexible and controllable, have the ability…
▽ More
The massive deployment of inverter-based generation poses several challenges to system operators but also offers new opportunities. In the context of grid recovery, inverter-based generation is expected to take over new responsibilities, as conventional generation that are blackstart capable are being decommissioned. Inverter-based facilities, being very flexible and controllable, have the ability to contribute during grid restoration, although it is still unclear how to deal with the limited ratings of batteries, PV, etc. and how to address nonlinear effects such as inrush currents or harmonics. In this direction, the requirements of grid-forming inverters to comply with black start capabilities are still to be defined. During the first steps of a grid restoration process the dynamics of the grid largely vary from the grid behaviour under normal operation. In particular, the grid is nearly unloaded and therefore poorly damped. Indeed, overvoltages and resonances are a common concern during the energization of long transmission lines. In this work we analyse the spectral properties of unloaded transmission lines, and describe the impact of voltage controllers on the dam** of the system. As a byproduct, this analysis can be leveraged to propose high level requirements for grid-forming devices, in order to provide adequate dam** during the early stages of a grid restoration process.
△ Less
Submitted 25 May, 2024;
originally announced May 2024.
The impact of load placement on grid resonances during grid restoration
Authors:
Adolfo Anta,
Diego Cifelli
Abstract:
As inverter-based generation is being massively deployed in the grid, these type of units have to take over the current roles of conventional generation, including the capability of restoring the grid. In this context, the resonances of the grid during the first steps of a black start can be concerning, given that the grid is lightly loaded. Especially relevant are the low frequency resonances, th…
▽ More
As inverter-based generation is being massively deployed in the grid, these type of units have to take over the current roles of conventional generation, including the capability of restoring the grid. In this context, the resonances of the grid during the first steps of a black start can be concerning, given that the grid is lightly loaded. Especially relevant are the low frequency resonances, that may be excited by the harmonic components of the inverter. A typical strategy to avoid or minimize the effect of such resonances relies on connecting load banks. This was fairly feasible with conventional generation, but given the limited ratings of inverters, the amount of load that can be connected at the beginning is very limited. In this paper we consider the energization of a transmission line, and investigate the optimal location of a load along a line in order to maximize the dam** in the system. By analysing the spectral properties as a function of the load location, we formally prove that placing the load in the middle of the transmission line maximizes the dam** ratio of the first resonance of the system.
△ Less
Submitted 14 February, 2024;
originally announced February 2024.